Shopping security
The Honeywell 8C-PAIN01, also cataloged as the 51454356-175 Analog Input Module, operates as a dedicated hardware component for high-precision differential analog input signal conditioning within Experion PKS Series 8 C300 platforms.
| Parameter | Specification |
|---|---|
| Model | 8C-PAIN01 |
| Brand | Honeywell |
| Origin | United States |
| Weight | 0.5 kg |
| Dimensions | 5.1 cm x 26.7 cm x 17.8 cm |
| Operating Temp | -40 to +70 deg C |
| Power Consumption | Backplane powered via Series 8 carrier |
| Input Configuration | 16-Channel high-impedance differential voltage |
| Input Impedance | > 10 MOhms |
| Isolation Voltage | 1000 VDC field-to-logic (optical isolation) |
| Software Configurable Ranges | -40 to +40 mA, 0-20 mA, 0-10 V |
| Conversion Accuracy | +/-0.1% of Full Scale |
| Resolution | 0.01% of Full Scale |
| Common Mode Rejection (CMRR) | > 120 dB @ 60 Hz |
The module architecture incorporates a 4-20 mA HART loop protocol layer embedded within a high-impedance differential circuit design to achieve superior noise rejection in electrified process environments. Optical separation rated at 1000 VDC establishes a channel-to-backplane isolation barrier that stops transient spikes and ground loops from compromising the logic solver. The input stage maintains an input impedance greater than 10 MOhms, driving a fast analog-to-digital converter matrix that achieves a common mode rejection ratio (CMRR) exceeding 120 dB at 60 Hz.
Q: How is the signal input range configured on the 8C-PAIN01 hardware? A: The input ranges, including -40 to +40 mA, 0-20 mA, and 0-10 V configurations, are entirely software-selectable via the Experion PKS engineering environment. No physical hardware jumpers or DIP switches are required on the module board.
Q: What level of electrical overload protection is built into the analog channels? A: The input loops feature multi-stage overload protection circuits capable of withstanding a continuous 120% current overload for up to 2 seconds, and transient peaks reaching up to 150% of full scale for a maximum of 0.1 seconds.
Q: Can this module be hot-swapped while the C300 controller is online? A: Yes, the Series 8 mechanical architecture supports live hot-swap execution. The 8C-PAIN01 module can be removed from or inserted onto its associated I/O Termination Assembly (IOTA) without disrupting power or data transmission to adjacent modules on the carrier.
Ships within 48 hours · Estimated delivery Jun 21 - Jun 26
US$40
Get nowSign up to your membership to get coupons up to
15%
Get nowOpportunity to enjoy order discount up to 15% off
Top-Converting Item to Boost Your Average Order